Product Description
Characteristic of Our AHF/APF:
- Unbalance compensation
- for harmonics or reactive power first;
- The protection level of the system reaches IP20;
- Can withstand 2.5 times overload of 10ms.
- The CT can be installed on the load side or the grid side according to the user's choice. The device can be automatically compatible with the CT phase sequence.
- By setting, you can choose whether to compensate
- Other basic functions
- Balance the three-phase current of the system to avoid single-phase overload of the transformer and improve the effective use capacity;
- Harmonic filtering function
- Up to 51 harmonics can be filtered out;
- Within the capacity range, the effective filtering ability of the target harmonics reaches 97%;
- Select and filter all the harmonics within 51 times at the same time, and set the filtering ratio of each harmonic;;
- With fast harmonic compensation, response time ≤5ms;
- Reactive compensation function
- With reactive power compensation capability, that is power factor adjustment capability;
- Provide two reactive power compensation modes : 1) constant reactive power mode; 2)constant power factor mode;
Product Model Description:
Product Parameters:
Rated compensation conventional capacity |
50A |
80A |
100A |
120A |
150A |
200A |
Rated overload capacity |
1.2 times rated current /1 min, 2.5 times rated current /10ms |
Wiring mode |
Three-phase four-wire system (three-phase three-wire system can be customized) under AC380V Voltage class Three-phase three-wire system under AC690V Voltage class |
Cooling method |
Air cooling |
Ambient temperature |
40°C , up to 55°C , 2%/K over-temperature automatic derating |
Parallel operation |
Support multi-machine parallel connection, can not equal capacity parallel |
Communications protocol |
RS-485, Modbus-RTU communication protocol |
Rated operating voltage |
AC380V±20% |
AC690V±15% |
Air cooling requirements (full load) |
≥330m3/h |
≥600m3/h |
≥1000m3/h |
≥1200m3/h |
≥1200m3/h |
≥1000m3/h |
Noise level |
≤ 60dB |
≤ 65dB |
Harmonic filtering range |
2-51 times |
Function set |
Combination of harmonic compensation, reactive compensation, unbalance compensation and free compensation with priority |
Dry contact |
One input contact: control switch machine; three output contacts: running power failure |
Altitude |
≤ 3000 m |
Voltage class |
AC380V±20%,AC690V±20% |
Rated operating frequency |
50Hz±5% |
Response time |
< 5ms |
Transformer installation location |
Power side / load side |
Dimension(mm) Wallmount |
400x190x570 |
450 x 200 x 620 |
480 x 270 x 707 |
|
(width x depth x height) Drawer |
530x550x190 |
530 x 550x190 |
475 x 600 x 270 |
550x600x270 |
Weight (kg) |
25 kg |
35 kg 70 kg |
70 kg |
62 kg |
Protection class Standard IP20 |
Certification |
Type test report of National Electronic Control and Distribution Equipment Quality Supervision Center, China Taier Laboratory Inspection Report |
The Perfect Filtering Result of our AHF/APF on A Actual Site in the Beautiful North Europe:
Before the AHF/APF on, the THDi is 23.8%
|
After the AHF/APF on, the THDi is dropped to 6%
|
Packaging & Shipping
To be packeged in wooden box and to be shipped By Sea or By air
1) Commissioning/Debugging On-Site;
2) Commissioning/Debugging Remote Online;